Asset ID,Asset Type,Location,Flood Vulnerability (1-5),Wind Vulnerability (1-5),Notes TR1-MPF-001,Main Power Feed,Basement,5,1,Critical utility ingress point. Located below sea level with no current flood mitigation. TR1-HVC-001,HVAC Chillers,Basement,5,1,Main cooling system for Data Halls A & B. Prone to complete failure in a flood event. TR1-GEN-001,Backup Generators,External Platform,2,4,Visible corrosion on support structure. Exposed to salt spray and high winds. TR1-FTK-001,Fuel Tanks,External Platform,3,3,Supplies fuel for backup generators. Anchor bolts show signs of rust. TR1-ANT-001,Communications Antenna,Roof,1,5,Primary satellite link. Mountings have not been inspected since installation. TR1-SVR-A01,Server Racks,Data Hall A (1st Floor),2,1,"Located on raised flooring, but floor is not sealed from basement below." TR1-UPS-001,UPS Battery Banks,Basement,5,1,Battery room is adjacent to main power feed. No dedicated sump pump installed. TR1-HVC-002,HVAC Rooftop Units,Roof,1,4,Secondary cooling system. Panels and shrouds show damage from previous storm. TR1-SVR-B01,Server Racks,Data Hall B (2nd Floor),1,1,Considered the most secure asset location in the facility. TR1-FBR-001,Fiber Optic Entry,Basement,4,1,Main network ingress point. Conduit is not water-tight.